What are the common faults and treatment methods of variable frequency AC motors?

Nov 18, 2024 Leave a message

1. Electrical fault:
1. Winding fault:
Winding break: The motor may not start normally or may make abnormal sounds or vibrations during operation. Use a multimeter to measure the resistance of the motor winding. If the resistance of a phase is infinite or obviously abnormal, it can be determined that the winding of that phase is broken. The treatment method is to rewind or replace the damaged winding.
Interphase short circuit: When the motor is running, the current increases abnormally and the heat is severe, which may even cause the inverter protection to trip. During inspection, the insulation resistance between the windings can be measured by a megohmmeter. If the resistance value is too low, there may be an interphase short circuit. The short-circuited part needs to be repaired, and the entire winding needs to be replaced in severe cases.
Three-phase unbalanced winding: The three-phase current is unbalanced when the motor is running, which may cause the motor to vibrate and heat unevenly. Use a multimeter to measure the resistance value of the three-phase winding. If the three-phase resistance is greatly different, there is a three-phase unbalanced fault. Check whether the winding connection is correct. After eliminating the connection problem, repair or replace the unbalanced winding.
2. Insulation failure:
Insulation failure between winding and housing: The motor housing may be energized, endangering personal safety, and the motor performance will be reduced. Use a megohmmeter to measure the insulation resistance between the winding and the housing. If the resistance value is lower than the specified value, it indicates insulation failure. Check the insulation of the motor, find out the damaged parts of the insulation and repair them, such as re-wrapping the insulation material, replacing the insulation parts, etc.
3. Inverter parameter setting failure:
Improper parameter setting: The motor may not start normally, the speed may be unstable, or the expected speed regulation effect may not be achieved. For example, the acceleration and deceleration time is set too short or too long, and the torque boost setting value is inappropriate. The inverter parameters need to be correctly set according to the load characteristics and actual needs of the motor.
2. Mechanical failure:
1. Bearing failure:
Bearing wear: The motor will generate abnormal noise and vibration when it is running, and the vibration and noise will gradually increase over time. Check the bearing wear regularly and replace new bearings if necessary. At the same time, pay attention to keeping the bearings well lubricated, choose the appropriate grease, and fill it according to the prescribed time and method.
Bearing overheating: The bearing temperature is too high, which may be caused by poor lubrication, overload, improper installation, etc. Check the lubrication of the bearing to ensure the quality and filling amount of the grease are appropriate; check whether the load of the motor exceeds the rated value. If there is an overload, the load should be reduced; check whether the bearing is installed correctly. If there is a deviation, it should be reinstalled.
2. Excessive motor vibration:
Rotor imbalance: The mass distribution of the motor rotor is uneven, causing the motor to vibrate during operation. The balance of the rotor can be detected by dynamic balancing test, and the unbalanced parts can be weighted or adjusted to make the rotor reach a balanced state.
Unsound installation foundation: The foundation of the motor installation is not firm or the level is not enough, which will cause the vibration of the motor. Check the installation foundation of the motor to ensure that the foundation is firm and the level meets the requirements. If necessary, re-reinforce the foundation or adjust the level.
3. Overvoltage fault:
Cause: The overvoltage of the inverter is concentrated on the branch voltage of the DC bus. It may be caused by reasons such as too high power supply voltage, too short deceleration time, and excessive load inertia.
Treatment method: First, extend the deceleration time so that the motor has enough time to release energy during the deceleration process; second, install the brake unit and brake resistor to consume the feedback energy generated by the motor during the deceleration process; third, check whether the power supply voltage is normal. If it is too high, measures should be taken to reduce the power supply voltage.
4. Undervoltage fault:
Cause: Damage to one of the rectifier bridges, abnormal operation of the three thyristor circuits, damage to the main circuit contactor, and failure of the voltage detection circuit may all lead to undervoltage faults. In addition, the lack of phase in the input power supply may also cause undervoltage.
Treatment method: Check whether the rectifier bridge, thyristor, main circuit contactor and other components are working properly. If damaged, they should be replaced in time; check the voltage detection circuit and repair the fault point; check whether the input power supply is lacking in phase to ensure normal power supply.
5. Overcurrent fault:
Cause: It may be caused by phase-to-phase short circuit or short circuit to ground at the motor connection end, excessive load, too short acceleration and deceleration time parameter settings, and too large torque boost parameter settings.
Solution: Check the motor connection line and eliminate short circuit faults; reduce the load to avoid overload operation of the motor; adjust the acceleration and deceleration time parameters and torque boost parameters to meet the load characteristics and operating requirements of the motor. If the above methods cannot solve the problem, it may be a hardware failure of the inverter and the relevant components need to be replaced.
6. Overheating fault:
Cause: Poor motor heat dissipation, high ambient temperature, motor overload operation, etc. may cause the motor to overheat.
Solution: Check the ventilation of the motor, clean the blockage of the vents, and ensure good heat dissipation of the motor; improve the working environment of the motor and reduce the ambient temperature; check the load of the motor. If there is an overload, reduce the load or replace a motor with a higher power.